just built new home...and I need to run power to my pump shed, my electrician installed an disconect on my new home , but it only has 2 hot leads coming from it...my question is can i run only the 2 hot leads to well and then ground at pump with copper rod??
Reply to | Quote Reply | Add Photo
220 pump shed
candoarms
Join Date: Mar 2007 Posts: 1932 North Dakota Pics |
2008-02-24 151632
Ajp2927,
Your disconnect should be grounded at the box. The enclosure should serve as the ground connection. If you were to open the disconnect box, you'd likely find a ground wire attached to a ground terminal inside the case. This ground wire should be used when attaching your well pump to ground.
There may be two ground terminals inside your disconnect. One should be used by the power supply wire coming from the breaker box. The second ground screw should be attached to the power wire heading to your well pump.
You should check to be sure that your disconnect box is grounded back to the main circuit breaker box.
In any case, I wouldn't attempt to ground the pump using a copper grounding rod.
Joel ....